Reznor Heating Products Page

Model UDBS -
Separate Combustion


Size

Input Heating Capacity BTUH

Input Heating Capacity KWH

Thermal Eff.

Output Heating Capacity BTUH

Output Heating Capacity KWH

Gas Conn.
(in)

Air Volume CFM
( Max.)

Air Volume M3/min.
(Max.)

Fan
HP

Vent Size
( “ dia.)

Fan
Diameter ( in)

30

30000

8.8

82

24600

7.2

1/2

506

14.3

1/6

4

9X6

45

45000

13.2

82

36900

10.8

1/2

759

21.5

1/6

4

9X6

60

60000

17.6

82

49200

14.4

1/2

1012

28.7

1/3

4

9X6

75

75000

22

82

61500

18.0

1/2

1265

35.8

1/3

4

9X6

100

100000

30.8

83

87150

25.6

1/2

1793

50.8

3/4

4

10X10

125

125000

35.2

83

99600

29.2

1/2

2049

58.0

3/4

4

10X10

150

150000

43.9

83

124500

36.4

1/2

2562

72.5

1/4

5

12X12

175

175000

51.2

83

145250

42.5

1/2

2989

84.6

1/2

5

12X12

200

200000

58.6

83

166000

48.6

1/2

3419

96.7

1/2

5

12X12

225

225000

65.9

83

186750

54.7

3/4

3843

108.8

3/4

5

15X11

250

250000

73.2

83

207500

60.8

3/4

4270

120.9

3/4

5

15X11

300

300000

87.8

83

249000

72.9

3/4

5123

145.1

1-1/2

6

15X15

350

350000

102.5

83

290500

85.1

3/4

5977

169.2

2

6

15X15

400

400000

117.1

82

328600

96

3/4

6185

175.1

2

6

15X15



Note: Combustion air size for models 30 to 125 is 4” diameter. Combustion air size for models 150 to 250 is 5” diameter. Combustion air size for models 300 to 400 is 6” diameter.



Page 1 ... 2 .... 3 ....4 ( Click to advance page )





Proudly Representing/Installing /Servicing Reznor products since 1991



Agroponic Industries Ltd.
908 Ranchview Cres. NW, Calgary, Alberta, Canada, T3G 1P9
ph (403) 241-8234 / fax ( 403) 241-8238
e-mail : agropon@agroponic.com

File added to site 04/07/2004