Reznor Heating Products Page

Model UDAS -
Separate Combustion


Size

Input Heating Capacity BTUH

Input Heating Capacity KWH

Thermal Eff.

Output Heating Capacity BTUH

Output Heating Capacity KWH

Gas Conn.
(in)

Air Volume CFM

Air Volume M3/min.

Fan
HP

Fan RPM

Fan
Diameter ( in)

30

30000

8.8

82

24600

7.2

1/2

465

12.9

0.02

1550

10

45

45000

13.2

83

37350

11.0

1/2

629

17.8

0.03

1550

10

60

60000

17.6

83

49800

14.6

1/2

769

21.8

0.03

1550

12

75

75000

22

83

62250

18.3

1/2

961

27.5

0.06

1550

12

100

100000

30.8

83

87150

25.6

1/2

1345

36.7

1/30

1050

16

125

125000

35.2

83

99600

29.2

1/2

1537

45.9

1/20

1050

16

150

150000

43.9

83

124500

36.4

1/2

1921

54.4

1/6

1050

18

175

175000

51.2

83

145250

42.5

1/2

2242

63.5

1/6

1050

18

200

200000

58.6

83

166000

48.6

1/2

2562

72.5

1/6

1050

18

225

225000

65.9

83

186750

54.7

3/4

2882

81.6

1/4

1050

20

250

250000

73.2

83

207500

60.8

3/4

3202

90.7

1/4

1050

20

300

300000

87.8

83

249000

72.9

3/4

3843

108.8

1/2

1050

24

350

350000

102.5

83

290500

85.1

3/4

4483

126.9

1/2

1050

24

400

400000

117.1

83

332000

97.2

3/4

5123

145.1

1/2

1050

24



Note: Combustion air size for models 30 to 125 is 4” diameter. Combustion air size for models 150 to 250 is 5” diameter. Combustion air size for models 300 to 400 is 6” diameter.